Rainwater harvesting design, supply, and support.

Canadian Shield helps homeowners, cottages, businesses, and municipalities capture, store, and use rainwater effectively while meeting Ontario regulations.

Is rainwater harvesting legal in Ontario?

Yes — within regulated limits. The Ontario Building Code regulates how rainwater systems are designed, installed, and which uses they may supply; it does not prohibit collection. Non-potable uses such as toilet flushing and irrigation are standard practice in Ontario. Using harvested rainwater as drinking water requires treatment to the CSA B805 standard and local approval — the CMHC's guidance for homeowners is explicit that permitted uses vary locally, so check your municipality before designing for a use beyond non-potable supply.

What the Building Code requires in a system

Ontario's 2024 Building Code carries non-potable water system provisions (Part 7) that specify the treatment train for a rainwater system: a debris screen of 6 mm, a first-flush diversion of at least 0.3 litres per square metre of roof area, a calming inlet or settling chamber, sediment-entrainment prevention, and a 50-micron filter ahead of the tank when the water is used indoors — or treatment to the contaminant limits published in CSA B805/ICC 805, the joint Canadian and American rainwater harvesting standard. Evaporative heat-rejection discharge may not be connected to a rainwater harvesting system. Where a clothes washer is supplied by both rainwater and a potable supply, dual check valve backflow preventers are required at area and premise isolation points.

How systems are sized

The arithmetic starts with roof area and local rainfall: one millimetre of rain falling on one square metre of roof yields one litre of water. Demand then sets the target — irrigation, toilet flushing, laundry, cooling make-up, or process water each change the profile. CMHC suggests a working rule of thumb of capturing roughly 80% of annual runoff for typical household uses. Storage must cover first-flush volume and overflow on top of the demand figure, and Northern freeze-thaw cycles decide tank placement, burial depth and winterization.

What actually drives cost

No price table belongs here — every site differs — but the drivers are consistent: storage volume, treatment level (non-potable vs a path to potable), pumping and controls, winterization, roof condition, and the permit path in your municipality. A yield calculation against real rainfall data is what tells you whether a smaller tank at a better position beats a larger one.

Where it fits across our industries

Rural properties without municipal supply, seasonal properties reducing winterization load, campgrounds and resorts with summer-peaking demand, wineries and food sites with process-water needs, and northern communities working toward water security.

Frequently asked questions.

Is rainwater harvesting legal in Ontario?

Yes, within regulated limits. The Ontario Building Code regulates how rainwater systems are designed, installed and used rather than prohibiting collection. Non-potable uses such as toilet flushing and irrigation are standard; using harvested rainwater for drinking requires treatment to the CSA B805 standard and local approval.

What treatment does a rainwater system need under the Ontario Building Code?

The Building Code's non-potable water system provisions require a treatment train: a debris screen, a first-flush diversion of at least 0.3 litres per square metre of roof area, a calming inlet or settling chamber, and a 50-micron filter ahead of the tank when the water is used indoors — or treatment to the contaminant limits in CSA B805/ICC 805. Evaporative heat-rejection discharge may not be connected to a rainwater harvesting system.

How big should a rainwater cistern be?

Size starts with roof area and local rainfall — one millimetre of rain on one square metre of roof yields one litre of water — and then matches storage to demand. CMHC suggests a rule of thumb of capturing roughly 80% of annual runoff for typical uses; overflow and first-flush volumes must be added to the storage figure.

Have a remote, regulated, or difficult water/wastewater project?

Tell Canadian Shield what you are planning, where the site is, and what problem needs to be solved. The team can help identify the right next step.